Technical specifications for Booksize format

 

General technical specifications

Unless explicitly specified otherwise, the following technical specifications are valid for all components of the SINAMICS S120 booksize drive system.
 

Note:

When engineering the complete SINAMICS S120 drive, the system data of the associated Control Units, supplementary system components, DC link components and Sensor Modules must be taken into consideration.

Electrical specifications

Line voltage

380 ... 480 V 3 AC ±10 % (-15 % <1 min)

Line system configurations

Grounded TN/TT systems and non-grounded IT systems

Line frequency

47 ... 63 Hz

Electronics power supply

24 V DC -15 %/+20 %1), safety extra low-voltage (PELV/SELV)

Short-circuit current rating (SCCR)

(Short Circuit Current Rating)
according to UL 508C (up to 600 V)

1.1 ... 447 kW: 65 kA

Electromagnetic compatibility

According to EN 61800‑3

Second environment, Category C2/C3

For further information, see section Configuration notes

Overvoltage category

According to IEC/EN 61800‑5‑1

III

Mechanical specifications

Degree of protection

 

  • According to EN 60529

IP20

  • According to UL 508C/UL 61800‑5‑1

Open type

Protection class

 

  • Line circuits with protective conductor connection according to IEC 61800‑5‑1

I

  • Electronic circuits

Safety extra low-voltage PELV/SELV

Ambient conditions

 

Storage

Transport

Operation

In product packaging

In transport packaging

 

Climatic environmental conditions

Class 1K4
acc. to EN 60721‑3‑1
-25 ... +55 °C (-13 ... +131 °F)

Class 2K4
acc. to EN 60721‑3‑2
-40 ... +70 °C (-40 ...+158 °F)

Class 3K3 3)
acc. to EN 60721‑3‑3
For operation without derating4): 0 ... +40 °C (32 ...104 °F)
For operation with derating: >40 ... +55 °C (>104 ... 131 °F)

Relative humidity 5 ... 95 %

Environmental class/harmful chemical substances

Class 1C2
acc. to EN 60721‑3‑1

Class 2C2
acc. to EN 60721‑3‑2

Class 3C2
acc. to EN 60721‑3‑3

Organic/biological influences

Class 1B1
acc. to EN 60721‑3‑1

Class 2B1
acc. to EN 60721‑3‑2

Class 3B1
acc. to EN 60721‑3‑3

Pollution degree 2)

acc. to IEC/EN 61800‑5‑1

2

Installation altitude

 

  • Up to 1000 m (3281 ft) above sea level

Without derating

  • From 1000 m (3281 ft) up to 2000 m (6562 ft) )above sea level observe the derating characteristics
  • Reduction of the output current by 10 % per 1000 m (3281 ft) or
  • Reduction of the ambient temperature by 5 K per 1000 m (3281 ft)
  • From 2000 m (6562 ft) up to 4000 m (13123 ft) above sea level observe the derating characteristics

 

  • Power components
  • Reduction of the output current by 10 % per 1000 m (3281 ft) or
  • Reduction of the ambient temperature by 5 K per 1000 m (3281 ft)

and additionally:

  • Operation on line supply systems with grounded neutral point, or
  • Operation with an isolating transformer with secondary grounded neutral point
  • Control Units
  • Reduction of the ambient temperature by 5 K per 1000 m (3281 ft)

Mechanical strength

 

Storage

Transport

Operation

In product packaging

In transport packaging

 

Vibratory load

Class 1M2
acc. to EN 60721‑3‑1

Class 2M3
acc. to EN 60721‑3‑2

Class 3M1
acc. to EN 60721‑3‑3
Test valuesacc. to EN 60068‑2‑6 :
10 oscillations per axis in the range: 10 ... 57 Hz constant deflection 0.075 mm
57 ... 150 Hz constant acceleration 9.81 m/s2(1 × g)

Shock load

Class 1M2
acc. to EN 60721‑3‑1

Class 2M3
acc. to EN 60721‑3‑2

Class 3M1
acc. to EN 60721‑3‑3
Test valuesacc. to EN 60068‑2‑27 :
3 shocks per axis in both directions
Peak acceleration 49 m/s2 (5 × g); duration 30 ms

Certificates

Declarations of conformity

CE (Low Voltage, EMC and M​achinery Directive)

Certificates of suitability

cULus

 

1) When using a motor holding brake, restricted voltage tolerances (24 V ±10 %) might need to be taken into account.
 

2) The components must be protected against conductive pollution, e.g. by installing them in a control cabinet with degree of protection IP54 according to IEC 60529 or NEMA 12. If conductive pollution can be excluded at the installation site, a lower degree of cabinet protection is permissible.
 

3) Better than 3K3 through increased ruggedness regarding the temperature range and humidity. Oil mist, salt mist, ice formation, condensation, dripping water, spraying water, splashing water and water jets are not permitted.

4) Also carefully observe the permissible temperatures for the Control Unit and operator panel.

 

Chi tiết về sản phẩm SINAMICS S120 built-in units > Booksize format > Smart Line Modules in booksize format

 

Smart Line Modules are stall-protected, line-commutated infeed/regenerative feedback units (diode bridge for incoming supply; stall-protected, line-commutated regenerative feedback via IGBTs) with 100 % continuous regenerative feedback power. The regenerative feedback capability of the modules can be deactivated by means of a digital input (Smart Line Modules 5 kW and 10 kW) or by means of parameterization (Smart Line Modules 16 kW, 36 kW and 55 kW). Smart Line Modules are designed for connection to grounded TN/TT systems and non-grounded IT systems.
 

The DC link is pre-charged via integrated precharging resistors.

The associated line reactor is required for operating a Smart Line Module.

 

Design

The Smart Line Modules in booksize format feature the following connections and interfaces as standard:

  • 1 power connection via screw-type terminals
  • 1 connection for the 24 V DC electronics power supply via the 24 V terminal adapter included in the scope of supply
  • 1 DC link connection via integrated DC link busbars
  • 2 PE (protective earth) connections
  • 2 digital inputs
    (only for Smart Line Modules 5 kW (5 hp) and 10 kW (10 hp))
  • 1 digital output
    (only for Smart Line Modules 5 kW (5 hp) and 10 kW (10 hp))
  • 3 DRIVE‑CLiQ sockets
    (only for Smart Line Modules 16 kW (18 hp), 36 kW (40 hp) and 55 kW (60 hp))
  • 1 temperature sensor input for KTY84‑130, Pt1000 or PTC (only for Smart Line Modules 16 kW (18 hp), 36 kW (40 hp) and 55 kW (60 hp), Pt1000 can be used from firmware V4.7 HF17)

The status of the Smart Line Modules is indicated via two multi-color LEDs.

The signal cable shield can be connected to the Line Module by means of a shield connection terminal, e.g. Weidmüller type KLBÜ 3-8 SC.


The scope of supply of the Smart Line Modules includes:

  • DRIVE‑CLiQ cable for connecting the module to the adjacent Control Unit on the left with the drive control, length 0.11 m (4.33 in)
    (only for Smart Line Modules 16 kW (18 hp), 36 kW (40 hp) and 55 kW (60 hp))
  • 2 blanking plugs for closing unused DRIVE-CLiQ sockets
    (only for Smart Line Modules 16 kW (18 hp), 36 kW (40 hp) and 55 kW (60 hp))
  • DRIVE‑CLiQ cable (length depends on Smart Line Module width) for connection to the adjacent Motor Module, length = width of Smart Line Module + 0.11 m (4.33 in)
  • Jumper for connecting the 24 V DC busbar to the adjacent Motor Module
  • 24 V terminal adapter (X24)
  • Connector X21 for digital inputs and outputs
  • Connector X22 for digital inputs and outputs
    (only for Smart Line Modules 5 kW (5 hp) and 10 kW (10 hp))
  • Connector X1 for line connection
    (only for Smart Line Modules 5 kW (5 hp) and 10 kW (10 hp))
  • 1 set of warning labels in 30 languages
 

Integration

Connection example of 5 kW and 10 kW Smart Line Modules in booksize format

Connection example of 16 kW, 36 kW and 55 kW Smart Line Modules in booksize format

 

Technical specifications

 

Smart Line Module in booksize format

6SL313...

Line voltage

(up to 2000 m (6562 ft) above sea level)

380 ... 480 V 3 AC ±10 % (in operation -15 % <1 min)

Line frequency

47 ... 63 Hz

SCCR (short-circuit current rating)

65 kA in conjunction with the recommended Class J fuse, or circuit breaker according to UL489 / CSA 22.2 No. 5-02

see recommended line-side components

Line power factor

at rated power

 

  • Fundamental power factor (cos φ1)

>0.96

  • Total (λ)

0.65 ... 0.9

Overvoltage category

according to EN 60664‑1

Class III

DC link voltage, approx.

1.35 × line voltage1)

Electronics power supply

24 V DC -15 %/+20 %

Radio interference suppression

 

  • Standard

No radio interference suppression

  • With line filter

Category C2 to EN 61800‑3
Total cable length up to 350 m (1148 ft) (shielded)

Type of cooling

Internal air cooling (power units with increased air cooling using an integrated fan)

Permissible ambient and coolant temperature (air)

during operation for line-side components, Line Modules and Motor Modules

0 ... 40 °C (32 ... 104 °F) without derating,
> 40 ... 55 °C (104 ... 131 °F), see derating characteristics

Installation altitude

Up to 1000 m (3281 ft) above sea level without derating,
> 1000 ... 4000 m (3281 ... 13124 ft) above sea level, see derating characteristics

Declarations of conformity

CE (Low Voltage and EMC Directives)

Certificate of suitability

cULus

 

1) The DC link voltage is maintained at the mean value of the rectified line voltage. For further information, see section Configuration notes.

Line voltage 380 ... 480 V 3 AC

Smart Line Module in booksize format

Internal air cooling

6SL3130-6AE15-0AB1

6SL3130-6AE21-0AB1

6SL3130-6TE21-6AA4

6SL3130-6TE23-6AA3

6SL3130-6TE25-5AA3

Infeed/regenerative feedback power

 

 

 

 

 

 

  • Rated power Prated
           
  • At 380 V 3 AC

kW

5

10

16

36

55

  • At 460 V 3 AC 2)

(hp)

(5)

(10)

(18)

(40)

(60)

  • For S6 duty (40%) PS6

kW

6.5

13

21

47

71

  • Pmax

kW

10

20

35

70

91

DC link current

 

 

 

 

 

 

  • At 540/600 V DC

A

9.3/8.3

18.5/16.6

30/27

67/60

105/92

  • For S6 duty (40 %)

A

11

22

35

79

138

  • Maximum

A

16.6

33.2

59

118

178

Input current

 

 

 

 

 

 

  • Rated current
    at 380/400/480 V 3 AC

A

8.6/8.1/6.7

17/16.2/12.8

29/27.5/24.5

62/59/51

94/90/77

  • For S6 duty (40 %) at 400 V

A

10.6

21.1

35

76

106

  • At 400 V max.

A

15.7

31.2

57.5

112

130

Current requirement

24 V DC electronics power supply, max.

A

0.8

0.9

0.95

1.5

1.9

Current carrying capacity

 

 

 

 

 

 

  • 24 V DC busbars

A

20

20

20

20

20

  • DC link busbars

A

100

100

100

200

200

DC link capacitance

 

 

 

 

 

 

  • Smart Line Module

μF

220

330

710

1410

1880

  • Drive line-up, max.

μF

6000

6000

20000

20000

20000

Power loss 1)

kW

0.08

0.14

0.19

0.406

0.666

Cooling air requirement

m3/s (ft3/s)

0.008 (0.3)

0.008 (0.3)

0.016 (0.6)

0.031 (1.1)

0.044 (1.5)

Sound pressure level

LpA (1 m)

dB

<60

<60

<60

<65

<60

Line connection

U1, V1, W1

 

Screw-type terminals (X1)

Screw-type terminals (X1)

Screw-type terminals (X1)

M6 screw studs (X1)

M6 screw studs (X1)

  • Conductor cross-section

mm2

2.5 ... 6

2.5 ... 6

2.5 ... 10

2.5 ... 50

2.5 ... 95

Shield connection

 

Shield connection plate integrated into the connector

Shield connection plate integrated into the connector

Shield connection plate integrated into the connector

See Accessories

See Accessories

PE connection

 

M5 screw

M5 screw

M5 screw

M6 screw

M6 screw

Cable length, max.

(total of all motor power cables
and DC link)

 

 

 

 

 

 

  • Shielded

m (ft)

350 (1148)

350 (1148)

630 (2067)

630 (2067)

1000 (3281)

  • Unshielded

m (ft)

560 (1837)

560 (1837)

850 (2789)

850 (2789)

1500 (4922)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

50 (1.97)

50 (1.97)

100 (3.94)

150 (5.91)

200 (7.87)

  • Height

mm (in)

380 (14.96)

380 (14.96)

380 (14.96)

380 (14.96)

380 (14.96)

  • Depth

mm (in)

270 (10.63)

270 (10.63)

270 (10.63)

270 (10.63)

270 (10.63)

Weight, approx.

kg (lb)

4.7 (10.4)

4.8 (10.6)

7 (15.4)

10 (22.0)

17 (37.5)

 

1) Power loss of Smart Line Module at rated output including losses of 24 V DC electronics power supply.

2) Nominal HP ratings are provided for ease of assigning components only. The Line Module outputs are dependent on the Motor Module loading and are to be dimensioned accordingly.
 

Characteristic curves

Overload capability

Duty cycle with previous load

S6 duty cycle with previous load

S6 duty cycle with previous load
 

Derating characteristics

Output power as a function of ambient temperature

Output power as a function of total cable length

Installation altitude

- >1000 ... 4000 m (3281 ... 13124 ft) above sea level
  + Reduction of the output current by 10 % per 1000 m (3281 ft), or
  + Reduction of the ambient temperature by 5 °C (9 °F) per 1000 m (3281 ft)

- >2000 ... 4000 m (6562 ... 13124 ft) above sea level
  + Operation on line supply systems with grounded neutral point, or
  + Operation with an isolating transformer with secondary grounded neutral point
 